CANOVATE Mobile Data Centers — Now Available in Ukraine from ASI
A ready-to-deploy data center in a standard ISO container: from 30 to 210 kW of IT load, factory-built and tested, ready for deployment at any site.
Alliance System Innovations LLC (ASI), the official representative of CANOVATE Group in Ukraine, offers CANOVATE Mobile Data Center solutions. This is a fully equipped data center housed in a steel container. Racks, power supply, cooling, fire suppression, monitoring, and physical security are already integrated, configured, and factory-tested. The module arrives on-site ready for connection, eliminating the need to build a separate server room and spend months on design and construction.

CANOVATE Mobile Data Center in a standard ISO container
Mobile Data Center Configuration
- Racks: 42–47U high, server racks 600×1000 mm and network racks 800×1000 mm (W×D).
- Power supply: modular UPS with battery cabinets (10-minute standard autonomy, longer autonomy available as an option), distribution panel, managed IP-PDUs (20×C13 + 4×C19). N+N (2N) redundancy.
- Cooling: precision in-row DX air conditioners, 32 kW of cooling capacity each. N+1 redundancy, with hot-aisle and cold-aisle containment.
- Monitoring (DCIM): real-time monitoring of the entire container, including electrical equipment. Temperature and humidity, smoke, water leakage, door opening, and vibration sensors.
- Access control: biometric fingerprint readers on the entrance doors and on the sliding doors between the cold and hot aisles.
- Structured Cabling System (SCS): copper or fiber-optic infrastructure, with MTP/MPO solutions for fast connectivity.
- Video surveillance: IP66 cameras with PoE and ONVIF, 8-channel video recorder with a 6 TB hard drive.
- Fire suppression: automatic fire detection and localized gas fire suppression through nozzles. The system includes audible and visual alarms, manual activation, and emergency shutdown. FM-200 or Novec 1230 gas (inert gas available as an option).

Internal module layout
Key Advantages
- Rapid deployment. The module is delivered fully assembled, configured, and factory-tested, allowing it to be commissioned significantly faster than a traditional permanent data center.
- Mobility. Standard ISO container dimensions allow the module to be transported by road, rail, or sea. If required, it can be relocated to another site.
- Scalability. A single solution can accommodate from 5 to 26 racks, while additional modules can be added to expand capacity.
- High availability. Power is configured with 2N redundancy, while cooling is configured with N+1 redundancy.
- Protected enclosure. IP55 protection rating, trapezoidal steel construction with 50 mm insulation made of non-combustible stone wool (A1 class), and F60 fire resistance.
- Wide operating temperature range. The module operates from −20 to +50 °C, with operation down to −40 °C available as an option. The calculated service life is 25 years.
- Custom manufacturing to customer specifications. The configuration, equipment, and external container design can be adapted to the customer’s technical requirements.

Components of the 40-foot module: modular UPS, distribution panel, 19″ racks, in-row air conditioners, outdoor units, cable routes, and fire suppression system

external design options
Configurations
| 20 ft | 40 ft | 45 ft | 2×45 ft (combined) | |
|---|---|---|---|---|
| Model | CAN-CONT-20-XX | CAN-CONT-40-XX | CAN-CONT-45-XX | CAN-CONT-DBL45-XX |
| Dimensions L×W×H, mm | 6058×2438×2591 | 12192×2438×2896 | 13716×2438×2896 | 13716×4876×2896 |
| Weight with equipment, t | 5 | 12 | 15 | 28 |
| Racks (server + network) | 4+1 | 8+2 | 10+2 | 24+2 |
| IT load, kW | 30 | 90 | 120 | 210 |
| In-row air conditioners, pcs. | 2 | 4 | 5 | 8 |
| Modular UPS, kVA | 30 | 120 | 150 | 250 |
The cooling capacity of the in-row air conditioner is specified at a return air temperature of 35 °C and an outdoor temperature of 35 °C. Chilled-water (CW), CRAC/CRAH, and indirect evaporative cooling systems are available as options. At altitudes above 1,000 m, capacity decreases and is therefore taken into account during the calculation.

20 ft: 5 racks, up to 30 kW IT load

40 ft: 10 racks, up to 90 kW IT load

45 ft: 12 racks, up to 120 kW IT load

2×45 ft: 26 racks, up to 210 kW IT load
Applications
- Telecom operators and service providers: communication nodes, edge sites, and rapid capacity expansion.
- Defense sector: rapidly deployable field and backup computing nodes that can be relocated when required.
- Government and critical infrastructure: backup data centers and disaster recovery (DR) sites.
- Energy, industry, construction, and mining: data processing directly at remote facilities.
- Hosting and financial institutions: additional capacity without the need for construction.
- System integrators: a ready-to-deploy infrastructure platform for turnkey projects.
Why It Is Relevant for Ukraine
A mobile data center enables rapid recovery or relocation of IT infrastructure, or the creation of a backup site in another region. Instead of one large facility, organizations can build a distributed network of several compact nodes. The integrated UPS keeps the load running during the transfer to a generator. ASI can also complement the solution with backup and alternative power systems from its portfolio.
How to Order
ASI can help select a standard configuration based on your IT load or arrange the production of a customized module according to the customer’s technical specifications. We can calculate the project requirements and provide delivery throughout Ukraine with full project support. Partners and system integrators can register their projects on the website.